Fault Cause Remedy
Error during blow-down:
If blow-down is done incorrectly
or insufficiently, salts may be con-
centrated in the water. Therefore,
foaming can occur in the water,
and water can be carried away
during steam extraction.
Blow down the device every day
according to the operating instruc-
tions.
Boiler sucked up caused by
vacuum build-up.
Blow down.
Fill level detection defective Replace fill level detection
9.2 Defect, cause, remedy
CAUTION!
The facts and information listed as defects in this
chapter are described in such a way that they may
be eliminated by a person skilled in
– Electrics/electronics
– Mechanics/maintenance
.
The device components mentioned in the “Cause”
column are detailed in the supplied electric circuit
and pneumatic diagrams.
Defect Cause Remedy
Water emerging from the drain
hose
Safety valve leaking Check and adjust, if necessary.
Ä
Chapter 3.4.1 ‘Performing the
checks’ on page 21
Operating pressure for standard
version: 4 bar, max.
Operating pressure for cleaning
version: 5 bar, max.
Boiler is being overfilled Electrode dirty If yes: Remove electrode and
check for soiling (dirt, lime, rust);
clean electrode, if necessary.
Used electrodes need to be
replaced.
Remedy of faults/elimination of defects
Defect, cause, remedy
30.09.2022
Steam generator VEIT SG67
56