Setting Up the CRT
13-
3
Revision 4
13.5. Setting Thresholds
To set thresholds press F2.
Note: Shift/5 also accesses Thresholds.
Figure 47 - CRT Setup/Thresholds or F4/F2
Voltage and resistance thresholds can be set or changed outside of site setup. The Cellcorder indicates
an out of tolerance reading by beeping twice and displaying the reading in reverse video.
Site Is Not Selected
If a site is not selected, you can set up thresholds using CRT Setup/Thresholds F4/F2. The settings
remain in Cellcorder temporary storage until changed, cleared to default (zero) values or a site is
selected.
Site Is Selected
If a site is selected, you can change the thresholds using CRT SETUP/Thresholds F4/F2, but the changes
affect only the Cellcorder and not the site file. The settings remain in temporary storage until changed,
cleared to default or another site is selected.
Default Thresholds
If a site is selected, you can quit the site settings and return to default thresholds for voltage, resistance,
temperature, and Specific Gravity without affecting the site file.
To Clear Site Setup and Thresholds
To have no site associated with a file that has been linked, and to clear threshold settings, use the Clear
button on the Active Site LCD window.

Table of Contents

Other manuals for Vertiv Alber Cellcorder CRT-400

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv Alber Cellcorder CRT-400 and is the answer not in the manual?

Vertiv Alber Cellcorder CRT-400 Specifications

General IconGeneral
BrandVertiv
ModelAlber Cellcorder CRT-400
CategoryTest Equipment
LanguageEnglish