Vertiv | Liebert® DSE500™ Installer/User Guide | 42
Submenu ID Meaning
Comments
C00 EBM address
Do not change unless properly instructed.
C01 ZIEHL_ABEGG address
C02 FANS_TECH address
C03 EC Fan 1 model ID
C04 EC Fan 2 model ID
C05 EC Fan 3 model ID
C06 EC Fan 4 model ID
C07 System model ID "0" = Single, "1" = Dual
C09 System refrigerant type "2" = R407c, "3" = R410a
C10 Condenser pressure absolute max 1 R407c - 17-25 bar; 247-362 psi
C11 Condenser pressure absolute max 2 R410a - 25-38 bar; 363-550 psi
C12 Condenser pressure absolute min 1 R407c - 11-17 bar; 160-246 psi
C13 Condenser pressure absolute min 2 R410a - 16-24 bar; 232-347 psi
C14 Condenser pressure PID Kp
Do not change unless properly instructed.C15 Condenser pressure PID Kip
C16 Condenser pressure PID Kdp
C17 Refrigerant temperature max 1
Range 30 - 40°C; 86 - 104°F
C18 Refrigerant temperature max 2
C19 Refrigerant temperature min 1
Range 20 - 30°C, 68 - 86°F
C20 Refrigerant temperature min 2
C21 Refrigerant temperature PID Kp
Do not change unless properly instructed.C22 Refrigerant temperature PID Kip
C23 Refrigerant temperature PID Kdp
C24 System control state "0" = Manual, "1" = Auto
C25 Condenser pressure setting point 1 R407c - 12-18 bar; 174-261 psi
C26 Condenser pressure setting point 2 R410a - 18-26 bar; 261-376 psi
C27 Lee Temp Option
"0" - No Lee Temp installed,
"1" - Lee Temp installed
Table 8.2 Premium Efficiency Control Board Configuration-parameter List