Vertiv I Liebert Air Cooled Condenser I User Manual 9
4. Be careful not to damage the waterproof layer and observe the local regulations when the
condenser is installed on the roof of the building.
5. Position the condenser higher than the indoor unit to ensure normal oil return.
6. Follow the installation arrows on the condenser for correct installation direction.
2.3 Space Requirements
1. A 4000mm clearance is required around the condenser air outlet.
2. 600mm service spaces are required on the four sides of the condenser.
The condenser needs sufficient installation and service space around the installation place.
The specific space requirements are shown in Figure 2-3 and Figure 2-4.
Figure 2-3 Horizontal installation space requirement (unit: mm)
Figure 2-4 Vertical installation space requirement (unit: mm)
Airflow
Airflow
Airflow