Vertiv I Liebert Air Cooled Condenser I User Manual 23
T
able 3-6
Sub
menu ID
Significance Default
value
Range Remarks
C00 Running pressure Pset 13/13/21 11~15/11~15/19~23 Read and write
C01
Pressure controlling range
Pband
5/5/7 4~6/4~6/6~7 Read and write
C02
fMin
10%fp 10%fp~50%fp Read and write
C03
Maximum
fMax
fp 51%fp~100%fp Read and write
C04 Fan number 1 1~2 Read and write
C05
Pressure sensor type 2 or 1 1:voltage type;2:current
type;
Read and write
C06 Refrigerant type 1
1 : R22 ; 2 : R407C ; 3 :
R410A
Read and write
C07 Jump frequency 1(% fp) 0 0~100 Read and write
C08 Jump frequency 1 range 0.0 0.0Hz~0.5Hz Read and write
C09 Jump frequency 2(% fp) 0 0~100 Read and write
C10 Jump frequency 2 range 0.0 0.0Hz~0.5Hz Read and write
C11 Jump frequency 3(% fp) 0 0~100 Read and write
C12 Jump frequency 3 range 0.0 0.0Hz~0.5Hz Read and write
C13 Curve of frequency control, 0 0:V/F;1:V/F2 Read and write
C14 Manual mode 0 0:OFF;1:ON Read and write
C15
M
frequency
0 0%fp~100%fp
Read and write
C16 Software version 100 100~999 Read only
C17 Year of manufacture 11 0~99 Read only
C18 Month of manufacture 02 1~12 Read only
C19 Day of manufacture 28 1~31 Read only
C98 Clear alarm history 0 0~1(Clear alarm history) Read and write
C99 Resume the default values 0
0 ~ 1 (
values)
Read and write