EasyManua.ls Logo

Vertiv Liebert Mini-Mate MT048 - OPTIONAL FIELD INSTALLED CONDENSATE PUMP CONNECTION LOCATIONS 4 & 5 ΤΟΝ MODELS

Vertiv Liebert Mini-Mate MT048
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
REV : 1
REV DATE : 08/17
DPN004077
Page :1 /1
Form No.: DPN001040_REV4
OPTIONAL FIELD INSTALLED
CONDENSATE PUMP CONNECTION LOCATIONS
4 & 5 TON MODELS
LIEBERT MINI-MATE
VARIABLE CAPACITY
Power Supply from
Electric Service Power Block
in Fan/Coil Module.
Route wire down to avoid
obstructing filter removal.
3/4" (19mm) NPT-Female
Condensate Drain
Connection
Condensate Pump
Support Bracket
3/8" (9.5mm) Compression Fitting
Drain Connection
Drain Line (field supplied)
Notes:
1. 3/4" NPT-Male to 3/4" (19mm) flexible rubber tubing assembly supplied must
be installed between condensate drain and pump inlet fitting and secured.
2. The Auxiliary Float Switch included with pump must be field interlocked
with unit control to enable unit shutdown feature. Wire to Mini-Mate
terminal per unit schematic.
3. Refer to DPN003401 for installation instructions.
4. Condensate pump is energized through Mini-Mate Module.
Separate power supply is not necesary.
5. Condensate pump includes built in drain line check valve.
21.5
546mm
6.6
168mm
1

Table of Contents