MODEL NUMBER
PSA5-
500MT120/
PSA5-
500MT120TAA
PSA5-
700MT120/
PSA5-
700MT120TAA
PSA5-1000MT120/
PSA5-
1000MT120TAA
PSA5-1500MT120/
PSA5-1500MT120
Overload Capacity in Normal or
AVR mode
(measurement tolerance
±10%)
105% - alarm warning.
120% - alarm warning and shutdown after 1 minute
130% - alarm warning and shutdown after 10 seconds
150% - alarm warning and immediate shutdown
Overload Capacity in Battery
mode
(measurement tolerance
±10%)
120% - alarm warning and shutdown after 20 seconds
130% - alarm warning and shutdown after 10 seconds
150% - alarm warning and immediate shutdown
Protection Electronic (over current, short circuit w/ latching shutdown)
Battery Type Valve Regulated Lead Acid (VRLA) in compliance with UL1989
Battery Manufacturer / Model
Leoch / DJW12-
7.0
CSB / GP1272
Leoch / DJW12-9.0
CSB / HR1234W or UPS12460
Vertiv/PSA5-
24VBATTKIT
Leoch / DJW12-9.0
CSB / HR1234W or
UPS12460
Battery Quantity x VDC x Ah 1 x 12V x 7.0Ah 1 x 12V x 9.0Ah 2 x 12V x 9.0Ah
Battery Backed Outlets (5) NEMA 5-15R
Surge Only Outlets (5) NEMA 5-15R
Environmental Requirements
Operating Temperature, deg
(degC)
32-104 (0-40)
Operating Elevation, feet
(meter)
0-9,842 (0-3,000)
Relative Humidity 0-95% non-condensing
Storage Temperature, degF
(degC)
5 to 113 (–15 to 45)
Storage Elevation, feet (meter) 0-49,212 (0-15,000)
Audible Noise <40 dBA @ 3 ft (1m) from all sides
<45 dB @ 3 ft (1m)
from all sides
Agency
Safety cTUVus Listed (UL 1778, 5th Edition; CSA 22.2 No. 107.3:2014)
RFI / EMI FCC part 15 subpart B, CLASS B
Surge Immunity
EN61000-4-5, Level 2 (Line-Neutral)
EN61000-4-5, Level 3 (Line-Ground)
Transportation ISTA Procedure 1A
Table 5.1 PSA5 Specifications (continued)
Vertiv | Liebert® PSA5™ Installer/User Guide | 20