Vertiv | NetSure 7100 Series Quick Start Guide (QS582127000) | Rev. T
Figure 59:
List DG: -48 VDC / +24 VDC Distribution Panel, (14) -48 VDC Bullet/TPS/TLS Circuit Breaker/Fuse
Positions (with Return Busbar) and (12) +24 VDC Bullet/TPS/TLS Circuit Breaker/Fuse Positions
(with Return Busbar)
Figure 60:
List DH: -48 VDC / +24 VDC Distribution Panel, (10) -48 VDC Bullet/TPS/TLS Circuit Breaker/Fuse
Positions (with Return Busbar) and (16) +24 VDC Bullet/TPS/TLS Circuit Breaker/Fuse Positions
(with Return Busbar)
Obs
erve proper
polarity when making
load connections.
WARNING!
-
48
V
D
i
s
tr
i
bu
ti
o
n
+
2
4V
D
i
s
t
r
i
b
uti
on
L
OAD AND LOAD RETURN CONNECTIONS
1/4-20 Studs on 5/8” Centers
(Customer must supply
or order additional
hardware)
Maximum Lug Width:
0.625 inches.
Load
Connections
Load Return
Connections
Caution: 100 A circuit breakers and fuses can be used without a space
provided the continuous operating current in each 100 A device does not exceed 64 A.
A 175 A or greater circuit breaker shall have an empty mounting position between it
and any other overcurrent protective device.
Observe proper
polarity when making
load connections.
WARNING!
-
48
V
D
i
s
t
r
i
b
ut
i
o
n
+
2
4V
D
i
s
tr
i
bu
ti
on
LOAD AND LOAD RETURN CONNECTIONS
1/4-20 Studs on 5/8” Centers
(Customer must supply
or order additional
hardware)
Maximum Lug Width:
0.625 inches.
Load
Connections
Load Return
Connections
Caution: 100 A circuit breakers and fuses can be used without a space provided
the continuous operating current in each 100 A device does not exceed 64 A.
A 175 A or greater circuit breaker shall have an empty mounting position between it
and any other overcurrent protective device.