Vertiv | NetSure Rectifier Module User Manual (UM1R483000e3) | Rev. 1.0
10
NOMINAL
INPUT
VOLTAGE
PERCENT
OF FULL
LOAD
INPUT
CURRENT
(AMPERES)
INPUT
VA
INPUT
WATTS
POWER
FACTOR
EFFICIENC
Y
% HEAT
HEAT
DISSIPATIO
N
BTU/HR
25
3.473
724.09
711.06
0.982
94.14
142.16
50
6.772
1409.55
1400.95
0.994
95.39
220.35
75
10.134
2106.45
2100.13
0.997
95.43
327.45
100
13.577
2817.16
2810.96
0.998
95.05
474.73
208
110
14.982
3106.95
3100.11
0.998
94.85
544.71
120
16.117
3340.37
3333.02
0.998
94.59
615.20
240
0
0.521
125.64
14.80
0.118
--
50.49
25
3.046
732.96
709.58
0.968
94.27
138.72
50
5.886
1414.58
1397.89
0.988
95.62
208.90
75
8.762
2103.56
2092.62
0.995
95.68
308.43
100
11.719
2809.66
2800.11
0.997
95.36
443.28
110
12.950
3103.35
3094.04
0.997
95.15
511.98
120
13.901
3330.36
3320.04
0.997
94.96
570.90
NOTE! System output is initially adjusted to 53.5 volts DC as measured at the system sense
point at 50% of full load and nominal input. “Percent of Full Load” refers to percent of 51.7
amperes.
Table 4: Maximum Input Current in 60Hz Input
INPUT VOLTAGE
INPUT CURRENT (AMPERES)
176
19.2
NOTE! At 100% of full load with output adjusted to 58 volts DC as measured at the shelf
output terminals.
Efficiency Curve (Refer to Figure 4.)
Figure 4: Efficiency Curve (at 230Vac,50Hz)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv NetSure R48-3000e3 and is the answer not in the manual?

Vertiv NetSure R48-3000e3 Specifications

General IconGeneral
BrandVertiv
ModelNetSure R48-3000e3
CategoryPower Supply
LanguageEnglish

Related product manuals