Vertiv | NetSure Rectifier Module User Manual (UM1R483000e3) | Rev. 1.0
8
Regulation:
a) Static : Steady state regulation is ±0.6% as controlled within the rectifier for any and all
combinations of load from no load to full load, input voltage, and input frequency at a
constant ambient temperature. The associated system Controller may provide increased
regulation.
b) Dynamic : Response time200us and overshot5% for load changes at 50%-25%-50%
and 50%-75%-50% at rated output voltage and current, meets YD/T731-2008.
For any step load change within the range of 10% to 90% of full load within 1 milliseconds,
per Telcordia GR-947-CORE, the maximum voltage transient will not exceed 5% of the initial
steady state voltage within 250±10 microseconds. Recovery to within 1% of the initial
steady state voltage does not exceed 4 milliseconds.
Filtering:
a) Voice Band Noise: Complies with YD/T-731-2008.
1. Peak-peak voltage is 200mV at 0-20MHZ and normal output voltage. (YD/T-731-2008)
2. Psophometric noise is ≤ 2 mV typical at 220Vac input,53.5 Vdc output and 30% to 90% of
rated load for more than one rectifier.
b) Wide Band Noise: Complies with YD/T-731-2008.
1. Wideband noise emission is < 20 mV between 25HZ-20kHz according to ETS 300132-2 .
AC Input Ratings
Voltage: Nominal 208/220/230/240 volts AC, single phase, 3-wire, 50/60 Hz, with an
operating range of 200 to 250 volts. Acceptable input frequency range is 45 to 65 Hz.
Permitted Variation: 85 to 305 VAC.
Harmonic Content (THD): Meets EN61000-3-2. :
5% .from 50% to 100% of rated output current at 220Vac,50Hz, 53.5Vdc and 25°C;
15% for 20% rated output current at 220Vac,50Hz, 53.5Vdc and 25°C.
Inrush Current: Peak does not exceed 1.5 times of the peak value of the maximum steady-
state input current at full load,220 Vac input voltage, and for any duration of AC input
interrupts. Under the above conditions, standard AC distribution circuit breakers will not
trip.
Typical Input Data: 50 Hz input.
a) Refer to Table 1.
b) Maximum Input Current: Refer to Table 2.