51
Vertiv I VRC Self-Contained System I User Manual
Table 8-4 Refrigeration system faults and troubleshooting methods
Symptom
Probable Causes
Check Items and Handling Methods
The surface of the
evaporator has
serious
condensation.
Check whether the surface of
the evaporator is blocked
with debris.
Check the surface of the evaporator. Blockage may result
in uneven discharge of the condensate water.
Air volume
decrease
The air filter is blocked.
Periodically check the filter and replace it in a timely
manner to avoid reduction in air volume due to blockage.
The fan is faulty.
Check whether the fan is faulty. Table 8-2 describes the
diagnosis and handling methods.
Blockage of the evaporator
Check the surface of the micro-channel evaporator and
periodically handle the blockage problem.