Liebert® XDC™
50 & 60 Hz, 130 & 160kW Nominal Cooling Capacity;
ModelRevision5orHigher
User Manual

Table of Contents

Questions and Answers

  • S
    Sean RichardsonAug 17, 2025
    Why is my Vertiv Liebert XDC Freezer room becoming too warm?
    • U
      umaddenAug 17, 2025
      If the room is becoming too warm, several factors could be the cause. First, ensure the Vertiv XDC is turned on via the user interface. If it is already on, check the room's temperature and relative humidity, and lower the RH setpoint if needed to decrease the dew point, setting it to 50% or lower at a normal room temperature of 68°F (20°C). Also, verify that the Liebert XD cooling modules are on. Another potential issue is the minimum room temperature setpoint being too high, so check the setpoint in the User Setpoints menu. Finally, make sure the temperature/humidity sensors are correctly placed on the return air side of the primary air mover, away from unsealed areas.
  • R
    Russell CohenAug 20, 2025
    What to do if the Vertiv Liebert XDC Freezer pump/compressor will not energize?
    • C
      Christine ColemanAug 20, 2025
      If the pump/compressor of your Vertiv Freezer is not energizing, start by checking L1, L2, and L3 for the rated voltage to ensure there is main power. Next, check for and tighten any loose electrical connections. If those are fine, allow the pump to cool and check the amp draw in case overloads have tripped. Also, inspect the circuit breaker to the pump(s). Finally, consult the Checklist for Liebert XDC Startup on page 111 to verify correct phase wiring.
  • C
    Christine LoweAug 22, 2025
    How to troubleshoot a Vertiv Liebert XDC Freezer pump that will not run?
    • C
      Curtis MurphyAug 23, 2025
      To troubleshoot a Vertiv Freezer pump that won't run, first ensure all isolation valves on the pump suction and/or discharge are completely open. Next, verify that the Liebert XD cooling modules are turned on prior to starting the Liebert XDC. Check the alarm history on the Liebert XDC for low refrigerant temperature (high dew point), and if necessary, lower the humidity in the conditioned space to allow the Liebert XDC to operate at a lower temperature. Ensure the temperature-humidity sensors are correctly placed on the return air side of the primary air mover, away from unsealed doors or windows. Check the differential pressure settings of the pressure switch and manually adjust if not within 6 psi, ±1 psi (41 kPa, ±7kPa; 0.41 bars, ±0.07 bars).
  • M
    Mr. Cristian GouldAug 26, 2025
    Why does my Vertiv Liebert XDC (Pump) suddenly stop?
    • H
      Heather ValdezAug 26, 2025
      If your Liebert XDC (Pump) suddenly stops, it could be due to several reasons. Check the room's humidity and the location of the remote sensors, ensuring they are not in a cold area with poor airflow, which could indicate a low refrigerant temperature (high dew point). A loss of power could also be the cause; the Liebert XDC will automatically restart when power is restored. Additionally, a clogged filter/dryer or impeller could be the issue, so clean out any debris. Finally, a leak in the system causing a loss of charge could be the culprit; check the entire system for leaks and repair as necessary.
  • X
    xprattAug 28, 2025
    What to do if Vertiv Liebert XDC room becomes too cold?
    • M
      Melvin MorenoAug 28, 2025
      If the room is becoming too cold, it may be due to a lack of load in the room. If no cooling is required, turn the Liebert XDC off at the I/O button. Another possibility is that the minimum room temperature setpoint is too low; check the setpoint in the User Setpoints menu. Also, ensure the temperature-humidity sensors are correctly placed on the return air side of the primary air mover, away from unsealed doors or windows.
  • C
    Christina BuchananAug 31, 2025
    Why is the Vertiv Liebert XDC pump noisy?
    • E
      Evan GloverAug 31, 2025
      A noisy Vertiv Freezer pump can be attributed to a few potential causes. Cavitation due to vapor in the pump could be the issue, so check for adequate charge in the system. The pump rotating in reverse could also cause noise. Finally, worn motor bearings can also cause a pump to be noisy; if this is the case, replace the pump.
  • B
    Barbara JonesSep 3, 2025
    What causes the main 24VAC fuse to trip in my Vertiv Liebert XDC Freezer?
    • B
      brookefrostSep 3, 2025
      If the main 24VAC fuse trips, it could be due to shorts or loose connections, so check the wiring connections of the 24VAC circuit. Another possibility is a faulty circuit board, which would require replacing the circuit board.
  • D
    Danielle MooreSep 5, 2025
    How to troubleshoot actuator motors in Vertiv Liebert XDC?
    • H
      hlewisSep 5, 2025
      To troubleshoot actuator motors, check for 24VAC power between P2-1 and P2-4. If there is no signal from the control, check for 24VAC at P22-1 (close) or P22-3 (open). If the motor is not operating, unplug P22 completely off of the board, then jumper P22-5 to P2-4 for grounding, and jumper P22-1 to P2-1 to drive close. Remove the jumper to stop closing, and then jumper P22-3 to P2-1 to drive open. If the motor still fails to work, replace it.
  • A
    Ashley CallahanSep 8, 2025
    What causes unstable pump operation in a Vertiv Liebert XDC Freezer?
    • L
      Larry VillaSep 8, 2025
      Unstable pump operation can occur if the R-134a pump loop is overcharged. While the pump is running, ensure the R-134a receiver level is within recommended levels.
  • N
    nathanielcurrySep 12, 2025
    What can cause motor burnout in Vertiv Liebert XDC Freezer?
    • T
      Taylor BrownSep 12, 2025
      Motor burnout can be caused by welded contactor contacts or welded overload contacts in the control panel. Replace any defective components.

Summary

Important Safety Instructions

Product Description

Equipment Handling

Safety guidelines and procedures for moving and installing the unit, considering its top-heavy nature.

Installation

Electrical Considerations

General points about electrical connections and supply verification.

High Voltage Connections

Verifying voltage/frequency and connecting high voltage supply.

Connecting High-Voltage Cables

Step-by-step instructions for connecting high-voltage cables to the unit.

Refrigerant Piping and Filling

Filling the Pumped Circuit-R-134 a

Steps for charging the R-134a pumped circuit with refrigerant.

Filling the DX Circuit-R-407 C

Instructions for filling the R-407C DX circuit with refrigerant.

Installation Checklist

Liebert iCOM Control

iCOM Components and Functions

Overview of the iCOM controller's display and key functions.

Changing Operational Settings

How to adjust operational parameters like alarms and setpoints.

Start the Liebert XDC with Liebert iCOM

Checklist for Liebert XDC Startup

A step-by-step checklist for preparing the unit for startup.

Alarm Descriptions and Solutions

Alarm Descriptions

Detailed explanations of various alarm types and their causes.

System Shutdown Causes

Reasons why the unit might shut down.

Troubleshooting

Maintenance

Vertiv Liebert XDC Specifications

General IconGeneral
BrandVertiv
ModelLiebert XDC
CategoryFreezer
LanguageEnglish