2 Introduction
The reliability of the total generator set is entirely dependent on the quality of the installation. Nearly all problems are
caused by faults or inaccuracies which occur during the installation. It is therefore of utmost importance to follow and
check the points mentioned in the manual.
2.1 Generator set storage, before use
If the generator set is stored for a prolonged period, check the possible conditions of conservation in relation to the stor-
age environment and the type of packaging.
The engine is supplied with a protection treatment which is valid for 6 months from delivery date.
• Check for the coolant (coolant circuit). The engine supplied with a mixture to withstand storage temperature of -15°C
(5 °F).
ATTENTION
The raw water circuit could contain engine test bed water. Drain completely the raw
water circuit if the storage temperature is lower than 0°C (32°F).
• Verify the packages integrity.
• Humidity and salt corrosion could damages the engine and/or generator during their storage.
2.2 First engine start
• Read the owner’s manual.
• Verify the fuel feed line for possible leaks. Take care to avoid restrictions in the fuel line pipes.
• Check and verify the electrical connections.
IMPORTANT
Wrong connection of positive and negative from battery could provoke short circuit
and damage the engine.
IMPORTANT Wrong connection of generator terminals could damage the generator.
• Check the battery condition and state of charge.
• Check the raw water circuit, the connection and open the sea cock.
• Check the belt and belt tension.
• Check coolant level and oil level of engine, verify if fuel is available in the tank. Fuel tank must be clean!
• Start the engine, lets warm up the engine for few minutes without load.
• Verify for any leaks, verify the sea water pump, and verify the ush of water on exhaust system, verify that no warnings
on the control panel are displayed.
IMPORTANT
If you hear a strange noise, or vibration of the engine is extreme or black smoke is com-
ing out of the exhaust stop the engine immediately and ask for assistance.
When the temperature of the engine stabilizes at a temperature higher than normal it might be necessary to
bleed the coolant circuit.
2.2.1 Bleeding the coolant circuit:
• Switch o the engine of the generator set.
• Open the expansion tank cap to let the air escape.