VT8350 [ User Interface Guide ]
Conguration Parameters Default Value Signicance and Adjustments
Permit timeout
Default value: 0
Read Only
Permit Join Timeout
Allows ZigBee devices to join the Coordinator Room Controller for 180 minutes
from the moment it is set to ON. Once the timer elapses, no devices will be able
to join the network.
NOTE: Permit Join parameter must be set to ‘On’ to enable this feature.
Range: 0 or 180 minutes
Paired devices
Default value: 0
Read Only
Paired ZigBee Devices
Shows the number of ZigBee wireless devices currently paired with the Room
Controller. A maximum of 20 ZigBee wireless devices can be paired with each
Room Controller.
Display Readings: 0 to 20 devices