Series 769 FireLock NXT™ Preaction Valve 9
TRIM PACKAGES
Trim Packages Available for Vertical Installation:
1
Non-Interlocked, Penumatic
2
Non-Interlocked, Pneumatic/Electric
3
Single-Interlocked, Pneumatic
4
Single-Interlocked, Electric or Double-Interlocked, Electric (Electric-Pneumatic/Electric)
5
Double-Interlocked, Electric/Pneumatic
6
Double-Interlocked, Pneumatic/Pneumatic
Trim Packages Include:
1
Actuator(s)
2
Air Feed Manifold
3
All Required Pipe and Fittings
4
All Standard Trim Accessories
5
All Required Gauges
Actuators:
Series 776 Low-Pressure Actuator –
The Series 776 Low-Pressure Actuator is pneumatically actuat-
ed and requires only 13 psi/90 kPa minimum air pressure, regardless of the system supply pressure.
This actuator allows the system to operate with a low air or gas pressure of 7 psi/48 kPa. Request
submittal 30.46.
Series 767 Electric/Pneumatic Actuator –
The Series 767 Electric/Pneumatic Actuator provides a
single trip point for the pneumatic event and an integral electric actuator. This actuator requires only
13 psi/90 kPa minimum air pressure, regardless of the system supply pressure. This actuator allows
the system to operate with a low air or gas pressure of 7 psi/48 kPa. Request submittal 30.62.
Series 798 Double-Pneumatic Actuator –
The Series 798 Double-Pneumatic Actuator requires two
separate pneumatic activations in order to actuate the system. This actuator requires only 13 psi/
90 kPa minimum air pressure, regardless of the system supply pressure. This actuator allows the
system to operate with a low air or gas pressure of 7 psi/48 kPa. Request submittal 10.49.
Series 753-E Solenoid Valve –
The Series 753-E Solenoid Valve is designed for use with systems that
require electrical activation. Request submittal 30.32.
Optional accessories:
Series 746 Dry Accelerator –
The Series 746 Dry Accelerator can be used on pneumatic release
systems to improve response time. Request submittal 30.64.
Series 760 Water Motor
Alarm –
The Series 760 Water Motor Alarm is a mechanical device that
sounds when a sustained flow of water occurs (such as with an open sprinkler). Request submittal
10.38.
Series 75B Supplemental Alarm Device –
The Series 75B Supplemental Alarm Device is designed to
provide a continuous alarm for systems equipped with a mechanical device. Request submittal 10.53.
Series 75D Water Column Kit –
The Series 75D Water Column Kit is designed to minimize residual
water in the riser from collecting above the clapper. Request submittal 10.97.
Alarm Pressure Switch –
Alarm Pressure Switches are designed to activate electrical alarms and
control panels when a sustained flow of water occurs (such as with an open sprinkler).
Air Supervisory Pressure Switch –
Air Pressure Supervisory Switches are used to monitor system air
pressure and are available as low-pressure and high-pressure sensitivity.
Air Supply System -
The air supply system contains all components for establishing and maintaining
air in a pneumatic system. The compressor, low pressure alarms, ball valves, and required trim are
included in the air supply system.
Air Compressor
Air Dryer
Air Maintenance Device
Alarm Panels
Drain Connection Kit

Other manuals for Victaulic FireLock NXT 769 Series

Questions and Answers: