Series 769 FireLock NXT™ Preaction Valve 9
TRIM PACKAGES
Trim Packages Available for Vertical Installation:
1
Non-Interlocked, Penumatic
2
Non-Interlocked, Pneumatic/Electric
3
Single-Interlocked, Pneumatic
4
Single-Interlocked, Electric or Double-Interlocked, Electric (Electric-Pneumatic/Electric)
5
Double-Interlocked, Electric/Pneumatic
6
Double-Interlocked, Pneumatic/Pneumatic
Trim Packages Include:
1
Actuator(s)
2
Air Feed Manifold
3
All Required Pipe and Fittings
4
All Standard Trim Accessories
5
All Required Gauges
Actuators:
•
Series 776 Low-Pressure Actuator –
The Series 776 Low-Pressure Actuator is pneumatically actuat-
ed and requires only 13 psi/90 kPa minimum air pressure, regardless of the system supply pressure.
This actuator allows the system to operate with a low air or gas pressure of 7 psi/48 kPa. Request
submittal 30.46.
•
Series 767 Electric/Pneumatic Actuator –
The Series 767 Electric/Pneumatic Actuator provides a
single trip point for the pneumatic event and an integral electric actuator. This actuator requires only
13 psi/90 kPa minimum air pressure, regardless of the system supply pressure. This actuator allows
the system to operate with a low air or gas pressure of 7 psi/48 kPa. Request submittal 30.62.
•
Series 798 Double-Pneumatic Actuator –
The Series 798 Double-Pneumatic Actuator requires two
separate pneumatic activations in order to actuate the system. This actuator requires only 13 psi/
90 kPa minimum air pressure, regardless of the system supply pressure. This actuator allows the
system to operate with a low air or gas pressure of 7 psi/48 kPa. Request submittal 10.49.
•
Series 753-E Solenoid Valve –
The Series 753-E Solenoid Valve is designed for use with systems that
require electrical activation. Request submittal 30.32.
Optional accessories:
•
Series 746 Dry Accelerator –
The Series 746 Dry Accelerator can be used on pneumatic release
systems to improve response time. Request submittal 30.64.
•
Series 760 Water Motor
Alarm –
The Series 760 Water Motor Alarm is a mechanical device that
sounds when a sustained flow of water occurs (such as with an open sprinkler). Request submittal
10.38.
•
Series 75B Supplemental Alarm Device –
The Series 75B Supplemental Alarm Device is designed to
provide a continuous alarm for systems equipped with a mechanical device. Request submittal 10.53.
•
Series 75D Water Column Kit –
The Series 75D Water Column Kit is designed to minimize residual
water in the riser from collecting above the clapper. Request submittal 10.97.
•
Alarm Pressure Switch –
Alarm Pressure Switches are designed to activate electrical alarms and
control panels when a sustained flow of water occurs (such as with an open sprinkler).
•
Air Supervisory Pressure Switch –
Air Pressure Supervisory Switches are used to monitor system air
pressure and are available as low-pressure and high-pressure sensitivity.
•
Air Supply System -
The air supply system contains all components for establishing and maintaining
air in a pneumatic system. The compressor, low pressure alarms, ball valves, and required trim are
included in the air supply system.
•
Air Compressor
•
Air Dryer
•
Air Maintenance Device
•
Alarm Panels
•
Drain Connection Kit