7. TROUBLE SHOOTING TABLE
Proceed as follows for quick detection of common faults.
DC loads must be disconnected from the batteries and the AC loads must be
disconnected from the inverter before the inverter and/or battery charger is tested.
Consult your Victron Energy dealer if the fault cannot be resolved.
The battery voltage is too high
Ensure that the battery voltage
is within the correct value.
Processor in no function-mode
Disconnect mains voltage.
Switch front switch off, wait 4
seconds.
Pre-alarm alt. 1. The DC input
voltage is low
Charge the battery or check the
battery connections.
Pre-alarm alt. 2. The ambient
Place the inverter in a cool and
well-ventilated room, or reduce
Pre-alarm alt. 3. The load on the
inverter is higher than the
Pre-alarm alt. 4. Voltage ripple
on the DC input exceeds
1.25Vrms
Check the battery cables and
terminals.
Check the battery capacity;
Pre-alarm alt. 5. Low battery
voltage and excessive load
Charge the batteries, reduce
the load or install batteries with
a higher capacity. Use shorter
and/or thicker battery cables.
The inverter did cut out following
a pre-alarm
Check the table for the
appropriate course of action.