Problem Cause Solution
Alt 2: Battery temperature sensor faulty Unplug battery temperature sensor from the
MultiPlus.
Reset the MultiPlus by switching it off, then
wait for 4 seconds and switch it on again.
If the MultiPlus now charges normally, the
battery temperature sensor is faulty and needs
to be replaced.
MultiPlus 2kVA 230V
Page 17 Trouble Shooting Table