EasyManua.ls Logo

Victron energy Multiplus - Technical Data

Victron energy Multiplus
26 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8. Technical Data
MultiPlus 12/2000/80
MultiPlus 24/2000/50
MultiPlus 48/2000/25
PowerControl / PowerAssist Yes
Transfer switch 32A
INVERTER
Input voltage range
9,5 – 17V 19 – 33V 38– 66V
Output
Output voltage: 230VAC ± 2% Frequency: 50Hz ± 0,1% (1)
Cont. output power at 25°C (3) 2000VA
Cont. output power at 25°C 1600W
Cont. output power at 40°C 1400W
Cont. output power at 65°C 1000W
Peak power 3500W
Maximum efficiency in % 93 / 94 / 95
Zero-load power 10 / 11 / 11W
Zero-load power search mode 3 / 4 / 4W
CHARGER
AC Input Input voltage range: 187-265 VAC
Input frequency: 45 – 65 Hz
Charge voltage 'absorption' 14,4 / 28,8 / 57,6V
Charge voltage 'float' 13,8 / 27,6 / 55,2V
Storage mode 13,2 / 26,4 /52,8V
Charge current house battery (4) 80 / 50 / 25A
Charge current starter battery 1 A (12V and 24V models only)
Battery temperature sensor Yes
GENERAL
Programmable relay (5) Yes
Protection (2) a – g
Common Characteristics Operating temp. range: -40 to +65°C (fan assisted cooling)
Humidity (non-condensing): max 95%
ENCLOSURE
Common Characteristics Material & Colour: Steel/ABS (blue RAL 5012) Protection category: IP 21
Battery-connection M8 bolts
230V AC-connection Screw terminals 13 mm² (6 AWG)
Weight 15,2kg
Dimensions (h x w x d) 506 x 234 x 146 mm
STANDARDS
Safety EN-IEC 60335-1, EN-IEC 60335-2-29, EN 62109-1
Emission / Immunity EN 55014-1, EN 55014-2, EN-IEC 61000-3-2, EN-IEC 61000-3-3
IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-3
Road vehicles ECE R10-4
MultiPlus 2kVA 230V
Page 18 Technical Data