11
Control
Initial start-up/configuration
The control unit covers two setting ranges, which must be configured
separately:
H General control unit (described in the menu as "Control unitĂ001ĆA") for
general details, such as date and time
H Multi-boiler control unit (described in the menu as "Control unitĂ001ĆB") for
the control of multi-boiler systems, where boilers are enabled subject to
temperature.
¨ Both configurations must be completed. The control unit will not function
properly if the configuration is prematurely terminated.
First, switch ON the gas fired wall-mounted boilers, then the cascade
control.
General control unit
Preconditions: Operating levelĂ3 must be selected (see pageĂ10).
Select "General control unit" with , if "General
control unit" is not already displayed; confirm
with
.
Select "Configuration" with
; confirm with .
Select "Yes" with
/ ; confirm with .
Select the required language with
/ ;
confirm with
.
Select "Yes" with / , if you wish the time to
change automatically between summer and
wintertime; confirm with
.
Press
to return to "General control unit".
The "General control unit" configuration is now
completed.
5862Ă474ĂGB
Control unit 001ĆA
General
Configuration
Configuration
Yes
German
Summer/wintertime
auto Yes