1. Drain the DHW cylinder from the
DHW side.
!
Please note
Material losses may result
from draining with a vacuum
pump when the air vent valve
is closed.
Open the air vent valve during
draining.
2.
Remove cover A, flange insulation
B
and flange cover
E
.
3. Disconnect the DHW cylinder from
the pipework to prevent cleaning
agents and contaminants entering
the pipe system.
4. Remove loose deposits with a high
pressure cleaner.
!
Please note
Pointed or sharp cleaning
equipment will damage the
cylinder interior.
Only use plastic tools to clean
the inside.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)