Viessmann Vitodens 300 - Page 78

Viessmann Vitodens 300
132 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Displayed
fault c ode
Con-
st.
Weat -
her-
com-
p.
System
character-
istics
Cause Remedy
28 X X Controls
without
flow tem-
perature
sensor
(low loss
header)
System flow
temperature
sensor lead
break
Check the low loss
header sensor (see
page 87)
30 X X Burner
blocked
Boiler tem-
perature sen-
sor shorted
out
Check the boiler
temperature sensor
(see page 87)
38 X X Burner
blocked
Boiler tem-
perature sen-
sor lead break
Check the boiler
temperature sensor
(see page 87)
40 X Mixer
closes
Heating circuit
M2 flow tem-
perature sen-
sor shorted
out
Check the flow tem-
perature sensor
48 X Mixer
closes
Heating circuit
M2 flow tem-
perature sen-
sor lead break
Check the flow tem-
perature sensor
50 X X No DHW
heating
Cylinder tem-
perature sen-
sor/comfort
sensor/loading
sensor
shorted out
Check sensor s (se e
page 87)
58 X X No DHW
heating
Cylinder tem-
perature sen-
sor/comfort
sensor/loading
sensor lead
break
Check sensor s (se e
page 87)
Checking and acknowledging faults (cont.)
78
Troubleshooting
5692 537 GB