Coding in the delivered condition Possible change
Slope M2
d3:14 Heating curve slope =
1.4
d3:02
to
d3:35
Heating curve slope ad-
justable from 0.2 to 3.5
(see page 32)
Level A1
d4:0 Heating curve level = 0 d4:13
to
d4:40
Heating curve level ad-
justable from 13 to 40
(see page 32)
Level M2
d4:0 Heating curve level = 0 d4:13
to
d4:40
Heating curve level ad-
justable from 13 to 40
(see page 32)
Code 2
Calling up code 2
1. Press L and G simultaneously
for approx. 2 s; confirm with d.
2. Select the required coding address
with a or b; the address flashes.
Confirm with d; the value flashes.
3. Change the value with a or b;
confirm with d. The display briefly
shows "Accepted", then the
address flashes again. Any
address may be selected with a
or b.
4. Press L and G simultaneously
for approx. 1 s.
Encoding has been terminated.
Complete overview
The coding addresses are grouped according to the following function areas.
The respective function area is shown on the display.
The areas are scanned in the following order using a or b.
Code 1 (cont.)
41
Coding
5692 536 GB