Required coding Address
Set DHW temperature 3 at 40 °C (check delivered condition) 67:40
Integrating the control unit into the LON system
The LON communication module (accessories) must be plugged in.
Installation instructions
LON communication module
Note
Data transfer via the LON system can take 2 to 3 minutes.
Setting up LON user numbers
Adjust the user number via coding
address "77" (see below).
In a LON system, the same number
cannot be allocated twice.
Updating the LON user list
Only possible, if all users are connected and the control unit is programmed to
be fault manager (code "79:1").
1. Press L and d simultaneously
for approx. 2 s. User check has
been initiated (see page 31).
2. Press e. The user list is updated
after approx. 2 min. The user check
is completed.
Single boiler system with Vitotronic 050 and Vitocom 300
Boiler control
unit
Vitotronic 050 Vitotronic 050 Vitocom
User no. 1
Code "77: 1"
User no. 10
Code "77: 10"
User no. 11
Set Code "77: 11"
User no. 99
Further details regarding the individual steps (cont.)
30
Initial start-up, inspection, maintenance
5692 536 GB