Coding in the delivered condition Possible change
77 :1 LON user number 77 :2
to
77 :99
LON user number, adjus-
table from 1 to 99:
1-4 = boiler
5 = cascade
10 - ... = Vitotronic 050
99 = Vitocom
Note
Allocate each number
only once.
79:1 Control unit is fault
manager
79:0 Control unit is not fault
manager
7b:1 Send time via LON 7b:0 Do not send time via LON
7F:1 Detached house 7F:0 Apartment block
Separate adjustment for
holiday program and time
program for DHW heat-
ing, as option
80:1 With a 5 second time
delay for fault message;
message will be issued,
if a fault persists for at
least 5 seconds
80:0 Without time delay
80:2
to
80:199
Time delay adjustable
from 10 to 995; 1 step =
5 s
81:1 Automatic summer/win-
ter time changeover
81:0 Manual summer/winter
time changeover
81:2 The radio clock module
will be recognised auto-
matically
81:3 Accept time via LON
88 :0 Temperature displayed
in Celsius
88 :1 Temperature display in
Fahrenheit
90:128 Time constant for calcu-
lating adjusted outside
temperature 21.3 h
90:0
to
90:199
Fast (low values) or slow
(high values) matching of
the flow temperature,
subject to the set value
when the outside tem-
perature changes;
1 step = 10 min.
Code 2 (cont.)