Coding in the delivered condition Possible change
A5:5 With heating circuit
pump logic function
(economy circuit): Heat-
ing circuit pump OFF, if
the outside temperature
(AT) is 1 K higher than
the set room tempera-
ture (RT
set )
AT > RT
set + 1 K
A5:0 Without heating circuit
pump logic function
A5:1
to
A5:15
With heating circuit pump
logic function: Heating
circuit pump OFF, if (see
the following table)
Parameter address
A5:...
With heating circuit pump logic function: Heating
circuit pump OFF, if
1 AT > RT
Set + 5 K
2 AT > RT
Set + 4 K
3 AT > RT
Set + 3 K
4 AT > RT
Set + 2 K
5 AT > RT
Set + 1 K
6 AT > RT
Set
7
to
AT > RTSet - 1 K
15 AT > RT
Set - 9 K