Coding in the delivered condition Possible change
F2:8 Time limit for party
mode 8 hours or exter-
nal operating mode
changeover via key
*
1
F2:0 No time limit for party
mode
F2:1
to
F2:12
Time limit adjustable from
1 to 12 h
F5:12 Run-on time of the inter-
nal circulation pump in
heating mode
F5:0 No run-on time of the in-
ternal circulation pump
F5:1
to
F5:20
Run-on time of the inter-
nal circulation pump ad-
justable from 1 to 20 min
Burner
F8:–5 For the operation in re-
duced room tempera-
ture mode, the set room
temperature will be
raised (up to the tem-
perature limit set by
coding address F9) to a
value subject to the out-
side temperature, if the
outside temperature
falls below -5 °C, see
example on page 95.
Observe the setting of
coding address A3.
F8:+10
to
F8:–60
Limit for raising the tem-
perature in reduced
mode adjustable from
+10 to -60 °C
F8:–61 Function disabled
F9:–14 Below an outside tem-
perature of -14 °C, the
set room temperature
will be raised to the
value selected as set
room temperature, if the
system operates with
the standard room tem-
perature, see the exam-
ple on page 95
F9:+10
to
F9:–60
Limit for raising the set
room temperature to the
value selected for stan-
dard mode adjustable
from +10 to -60 °C
*1
Party mode ends automatically in heating program "rw" when the system changes
over to operation with standard room temperature.