Filling with the control unit switched ON
If the system is to be filled with the
control unit switched ON, the change-
over valve will be moved to its central
position via coding address "2F:2"
and the pump will be started. The
burner shuts down if this program is
activated via coding address "2F".
The program is automatically disabled
after 20 minutes, and the coding
address is set to "0".
Screed drying function
The screed function enables screeds
to be dried. For this, always observe
the details specified by the screed
manufacturer.
You can select various temperature
profiles.
Temperature profile: Diagram 1 (DIN 4725 part 4) code "F1:1"
Temperature profile: Diagram 2 (ZV parquet and flooring technology) code
"F1:2"
Control functions (cont.)
93
Function description