Reducing the heat-up time
During the transition from operation
with reduced room temperature to
operation with standard room tem-
perature, the boiler water or flow tem-
perature will be raised in accordance
with the selected heating curve. The
boiler water or flow temperature can
be automatically increased.
The value and duration of the addi-
tional increase of the set boiler water
temperature or flow temperature can
be adjusted in the coding addresses
"FA" and "Fb".
Example for the settings in the delivered condition
A Start with standard room tempera-
ture
B Set boiler water or flow tempera-
ture in accordance with the
selected heating curve
C Set boiler water or flow tempera-
ture in accordance with coding
address "FA":
50 °C + 20% = 60°C
D Duration of operation with raised
boiler water or flow temperature in
accordance with coding address
"Fb":
60 min
Control functions (cont.)
96
Function description
5692 536 GB