Manual VIPA System SLIO Chapter 2 Digital Input
HB300E - SM - Rev. 09/38 2-3
For wires with a cross section of 0.08mm
2
up to 2.5mm
2
.
2 6
3 7
4 8
1 5
1
2
3
4
5
6
7
8
26
37
48
15
DI
DC24V
0V
01
Pos. Function Type Description
1 DI 0 I Digital input DI 0
2 DC 24V O DC 24V for sensor
3 0V O GND
4 --- --- not connected
5 DI 1 I Digital input DI 1
6 DC 24V O DC 24V for sensor
7 0V O GND
8 --- --- not connected
I: Input, O: Output
Data VIPA 021-1BB00
Number of inputs 2
Nominate input voltage DC 24V (20.4 ... 28.8V)
Signal voltage "0" 0 ... 5V
Signal voltage "1" 15 ... 30V
Current consumption
5V
24V
55mA
---
Input filter time delay 3ms
Input current typ. 3mA (EN 61131-2, type 1)
Isolation 500Veff (field voltage to the bus)
Module ID 0001 9F82
Bit-width in the process image 2bits
Configurable no
Pin assignment
Technical data