EasyManua.ls Logo

VIPA 021-1BB00 - Page 33

VIPA 021-1BB00
102 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Manual VIPA System SLIO Chapter 2 Digital Input
HB300E - SM - Rev. 09/38 2-7
For wires with a cross section of 0.08mm
2
up to 2.5mm
2
.
2 6
3 7
4 8
1 5
1
2
3
4
5
6
7
8
26
37
48
15
DI
DC24V
0V
01
23
Pos. Function Type Description
1 DI 0 I Digital input DI 0
2 DC 24V O DC 24V for sensor
3 0V O GND
4 DI 2 I Digital input DI 2
5 DI 1 I Digital input DI 1
6 DC 24V O DC 24V for sensor
7 0V O GND
8 DI 3 I Digital input DI 3
I: Input, O: Output
Data VIPA 021-1BD40
Number of inputs 4
Nominate input voltage DC 24V (20.4 ... 28.8V)
Signal voltage "0" 0 ... 5V
Signal voltage "1" 15 ... 30V
Current consumption
5V
24V
55mA
---
Input filter time delay 3ms
Input current typ. 3mA (EN 61131-2, type 1)
Isolation 500Veff (field voltage to the bus)
Module ID 0008 9F84
Bit-width in the process image 4bits
Configurable no
Pin assignment
Technical data