Manual VIPA System SLIO Chapter 2 Digital Input
HB300E - SM - Rev. 09/38 2-9
For wires with a cross section of 0.08mm
2
up to 2.5mm
2
.
2 6
3 7
4 8
1 5
1
2
3
4
5
6
7
8
26
37
48
15
DI
DC24V
0V
DC24V DC24
0
2
4
67
5
3
1
Pos. Function Type Description
1 DI 0 I Digital input DI 0
2 DI 2 I Digital input DI 2
3 DI 4 I Digital input DI 4
4 DI 6 I Digital input DI 6
5 DI 1 I Digital input DI 1
6 DI 3 I Digital input DI 3
7 DI 5 I Digital input DI 5
8 DI 7 I Digital input DI 7
I: Input
Data VIPA 021-1BF00
Number of inputs 8
Nominate input voltage DC 24V (20.4 ... 28.8V)
Signal voltage "0" 0 ... 5V
Signal voltage "1" 15 ... 30V
Current consumption
5V
24V
60mA
---
Input filter time delay 3ms
Input current typ. 3mA (EN 61131-2, type 1)
Isolation 500Veff (field voltage to the bus)
Module ID 0005 9FC1
Bit-width in the process image 8bits
Configurable no
Pin assignment
Technical data