Manual VIPA System SLIO Chapter 3 Digital Output
HB300E - SM - Rev. 09/38 3-7
For wires with a cross section of 0.08mm
2
up to 2.5mm
2
.
2 6
3 7
4 8
1 5
1
2
3
4
5
6
7
8
26
37
48
15
DO
DC24V
0V
0V 0
V
0
2
4
67
5
3
1
Pos. Function Type Description
1 DO 0 O Digital output DO 0
2 DO 2 O Digital output DO 2
3 DO 4 O Digital output DO 4
4 DO 6 O Digital output DO 6
5 DO 1 O Digital output DO 1
6 DO 3 O Digital output DO 3
7 DO 5 O Digital output DO 5
8 DO 7 O Digital output DO 7
O: Output
Data VIPA 022-1BF00
Number of outputs 8
Nominal load voltage DC 24V (20.4 ... 28.8V)
Current consumption
5V
24V
65mA
15mA + load
Isolation 500Veff (field voltage to the bus)
Load resistive, inductive or lamp load
Output current (per channel) 0.5A (short-circuit proofed)
Switch rate
for resistive load
for ind. load (IEC947-5-1, DC13)
for lamp load
max. 1kHz
max. 0.5Hz
max. 10Hz
Module ID 0106 AFC8
Bit-width in the process image 8bits
Configurable no
Pin assignment
Technical data