Manual VIPA System SLIO Chapter 4 Analog Input
HB300E - SM - Rev. 09/38 4-9
For wires with a cross section of 0.08mm
2
up to 2.5mm
2
.
2 6
3 7
4 8
1 5
1
2
3
4
5
6
7
8
DC24V
0V
V V
AI
1
2
3
4
5
6
7
8
01
Pos. Function Type Description
1 +AI 0 I + Channel 0
2 -AI 0 I Ground Channel 0
3 --- --- not connected
4 --- --- not connected
5 +AI 1 I + Channel 1
6 -AI 1 I Ground Channel 1
7 --- --- not connected
8 --- --- not connected
I: Input
The parameter data may be accessed during runtime with the following
record sets:
Record set
No. Byte
Meaning Default
128 0 Function-number channel 0 10h
129 0 Function-number channel 1 10h
In the following there are the measuring ranges with function-number listed,
which were supported by the analog module. With FFh the corresponding
channel is deactivated.
The formulas listed here allow you to transform an evaluated measuring
value (digital value) to a value assigned to the measuring range (analog
value) and vice versa.
Measuring range
(function number)
Voltage (U) Decimal (D) Hex Range Formulas for
calculation
11.76 32511 7EFFh overrange
10V 27648 6C00h
5V 13824 3600h
0V 0 0000h
nominal range
0 ... 10V
Siemens S7 format
(10h)
-1.76 -4864 ED00h underrange
10
27648
U
D ⋅=
27648
10
⋅= DU
12.5 20480 5000h overrange
10V 16384 4000h
5V 8192 3600h
0V 0 0000h
nominal range
0 ... 10V
Siemens S5 format
(20h)
-2 -3277 F333h underrange
10
16384
U
D ⋅=
16384
10
⋅= DU
Pin assignment
Parameter data
Function-number
channel x