Manual VIPA System SLIO Chapter 5 Analog Output
HB300E - SM - Rev. 09/38 5-15
For wires with a cross section of 0.08mm
2
up to 2.5mm
2
.
2 6
3 7
4 8
1 5
1
2
3
4
5
6
7
8
DC24V
0V
AO
1
2
3
4
5
6
7
8
01
23
Pos. Function Type Description
1 AO 0 O Channel 0
2 AGND O Ground channels
3 AO 2 O Channel 2
4 AGND O Ground channels
5 AO 1 O Channel 1
6 AGND O Ground channels
7 AO 3 O Channel 3
8 AGND O Ground channels
O: Output
The parameter data may be accessed during runtime with the following
record sets:
Record set
No. Byte
Meaning Default
0 1 Bit 0: Short-circuit recognition channel 0 (1:on)
Bit 1: Short-circuit recognition channel 1 (1:on)
Bit 2: Short-circuit recognition channel 2 (1:on)
Bit 3: Short-circuit recognition channel 3 (1:on)
Bit 7 ... 4: reserved
00h
128 0 Function-number channel 0 10h
129 0 Function-number channel 1 10h
130 0 Function-number channel 2 10h
131 0 Function-number channel 3 10h
Pin assignment