Manual VIPA System SLIO Chapter 5 Analog Output
HB300E - SM - Rev. 09/38 5-21
In the following there are the measuring ranges with function-number listed,
which were supported by the analog module.
With FFh the corresponding channel is deactivated.
The formulas listed here allow you to transform an evaluated measuring
value (digital value) to a value assigned to the measuring range (analog
value) and vice versa.
Output range
(function number)
Current (I) Decimal (D) Hex Range Formulas for
calculation
23.49 32511 7EFFh overrange
20mA 27648 6C00
10mA 13824 3600
0mA 0 0
nominal range
0 ... 20mA
Siemens S7 format
(31h)
Not possible, is limited to 0mA. underrange
27648
20
= DI
20
27648
I
D =
25.00mA 20480 5000h overrange
20mA 16384 4000
10mA 8192 2000
0mA 0 0
nominal range
0 ... 20mA
Siemens S5 format
(41h)
Not possible, is limited to 0mA. underrange
16384
20
= DI
20
16384
I
D =
Output range
(function number)
Current (I) Decimal (D) Hex Range Formulas for
calculation
22.81mA 32511 7EFFh overrange
20mA 27648 6C00
12mA 13824 3600
4mA 0 0
nominal range
4 ... 20mA
Siemens S7 format
(30h)
1.19mA -6912 E500h underrange
4
27648
16
+= DI
16
4
27648
=
I
D
24.00mA 20480 5000h overrange
20mA 16384 4000
12mA 8192 2000
4mA 0 0
nominal range
4 ... 20mA
Siemens S5 format
(40h)
0mA -4096 F000h underrange
4
16384
16
+= DI
16
4
16384
=
I
D
Function-number