EasyManua.ls Logo

VOKERA Vision C - Page 20

VOKERA Vision C
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18
NOTE

suitable alternative that will provide satisfactory weatherproof-


-

• The vertical terminal is supplied with a built-in converter box
and cannot be shortened.
• A 130mm hole is required for the passage of the concentric
terminal through the ceiling and/or roof.
Depending on site conditions it may be preferable to install the

-



ensuring that the exhaust pipe connects to the exhaust con-
nection on the concentric to twin converter.

allow connection to the concentric to twin converter.
NOTE
• 
made for connection onto the previous piece and onto the
 
be pushed 50mm onto the male spigots of the concentric to
twin converter.
• -
ported and connected.
• Ensure that any horizontal sections of pipe have a fall
of between 1 & 3º towards the appliance (1º =17mm per
1000mm).
Fig. 21
Fig. 22
Fig. 19

-

• The horizontal terminal is supplied with a built-in converter
box and cannot be shortened.
• A 130mm hole is required for the passage of the concentric
terminal through the wall.
• The air inlet pipe must always be level with or below, that of
the exhaust pipe.
Depending on site conditions it may be preferable to install the

Mark and drill a level 130mm hole for the passage of the horizontal


box ensuring that the exhaust pipe connects to the exhaust
connection on the concentric to twin converter.

allow connection to the concentric to twin converter.
NOTE
   
made for connection onto the previous piece and onto the

pushed 50mm onto the male spigots of the concentric to twin
converter.

Insert the exhaust connection manifold (A) onto the appliance

• Remove the blanking plate (located to the left of the appliance

plate (B).
• Using the hole in the exhaust connection manifold as a guide,


provided (C).
• Using the two holes in the air inlet plate as a guide, drill a
3mm hole in each and secure the air inlet pipe/bend using
the screws provided.
 
installed by pushing together (the plain end of each extension
or bend should be pushed approximately 50mm into the female
socket of the previous piece).
B
A
C
Fig. 20
1-deg = 17mm

Table of Contents

Related product manuals