9. Error codes & Solutions
Check the water circuit system, the opening
of by-pass kits, the running of water pump
Water flow switch
disconnected
Check the wiring and reconnect water flow
switch
Water flow switch defective
Ambient/Inlet water temp. is
too low and the unit is on
standby
The unit will be re-started when the
ambient/inlet water temp. goes up.
Check the water circuit system, the opening
of by-pass kits, the running of water pump
Ambient/ Water temp. is too
high
Fan motor speed is abnormal
or fan motor has damaged
Readjust the refrigerant volume
High pressure switch
disconnected or defective
Reconnect or replace high pressure switch
Check the installation circumstance. Clean
the evaperator. Check the running situation
of fan.
Low pressure switch
disconnected or defective
Reconnect or replace low pressure switch
Gas leakage (Check the
gauge)
Detect the leakage point and make the
maintainence
Fan motor speed is abnormal
or fan motor has damaged
EEV blocked or piping system
jammed
Connection failure between
PCB and controller
Communication failure
between PCB and driver
module
Change a new driver module
Check the water circuit system/ water flow
switch
Check if there is a gas leakage