4.6 Service – System Messages
Display of system information
Display Description Correction
System Messages
All system messages are displayed with a blinking caution symbol.
In case of sensor errors the sensor in question is also marked with short circuit or interruption symbols.
Interruption
Displayed sensor or line connection interrupted
/ defunct.
●
Check the resistance value of the sensor and
compare to the resistance table.
●
Check all contact points up to the sensor.
Short circuit
There is a short circuit of the sensor on the
display, the line or the sensor input on the
controller.
dT too high
A fixed value of 20 K is added to the
temperature difference between collector (T1)
and tank sensor (T2). The message is displayed
if after 30 minutes the total temperature
difference has not been reduced.
●
Check pump/pump connections/wiring.
●
Check system for air, and vent if required.
●
Check sensors/sensor lines and change sensor if
required.
4.7 Service – Sensor Control
Resistance values for Pt1000-sensors in relation to the temperature
-10°C 0°C 10°C 20°C 30°C 40°C 50°C 60°C 70°C 80°C 90°C 100°C 110°C
961 Ω 1000 Ω 1039 Ω 1078 Ω 1117 Ω 1155 Ω 1194 Ω 1232 Ω 1271 Ω 1309 Ω 1347 Ω 1385 Ω 1423 Ω
The working condition of the sensor can be checked with this table and an Ohm meter.
!