4.2 Information Menu
Information menu
Menu item Description Display
Collector temperature; Current value °C
Collector temperature; Balance value; minimum, resettable °C
Collector temperature; Balance value; maximum, resettable °C
Tank temperature, lower half; Current value °C
Tank temperature, lower half; Balance value; minimum, resettable °C
Tank temperature, lower half; Balance value; maximum, resettable °C
Tank temperature, upper half
1
; Current value °C
Operating hours, total; Current value h
Reset operating hours since last reset
Balance value, display, resettable;
h
Pump symbol idle: Function display
Temperature difference between collector and tank
is smaller than switch-on difference (solar circulation pump off).
—
Pump symbol active: Function display
Temperature difference between collector and tank
is higher than switch-on difference (solar circulation pump on).
—
1
Sensor T3 (tank, upper half) is simply a measuring sensor, therefore it is not monitored by the sensor control.
4.3 Settings Menu
Settings menu
Menu item Description Range Base value
Temperature limitation tank, lower half 15 - 90 °C 85 °C
Switch-on difference between collector and tank 3 - 40 K 10 K
Switch-off difference between collector and tank 2 - 35 K 3 K
Minimum temperature where analysis of switch-on difference starts 5 - 90 °C 10 °C
Set point temperature difference the speed control adjusts to 2 - 50 K 10 K
Minimum speed of the solar circulation pump
10% increments
30-100% 30%
Maximum speed of the solar circulation pump
SECUSOL only!
30-100% 100%
Charge time (s) of the solar heating system with speed 100 %; in 10 s increments
SECUSOL only!
20 - 360 s 60 s
min
__°C
__°C
__°C
__°C
__°C
__°C
__°C
__h
min
max
max
__h
R
dT max
__K
dT min
__K
__°C
T max
__°C
T min
T start
__
d max
__
d min
__
__K
dT