EN-SUNGO-S_BA-0804-1122P200 5
Installation in the Solar Circulation Unit
Affix the SUNGO S with the appropriate screws to the
wall mounting bracket of the solar circulation unit.
Open up the cable ducts next to the centre crosspiece in
the bottom of the control.
Remove outer insulation of the cables in such way that
single isolated wires start as they enter the casing from
the bottom.
Hold the connectors with one hand while tightening the
screws in order to minimise pressure on the circuit board
and to avoid tearing the connectors off.
Last connection should be to mains.
If power is switched on now, 230V AC will be present on
the casing of the triacs.
3.2 Connecting Wires
Layout of the SUNGO S connections
All connections are made to the circuit board at the bottom
of the control. On the right hand side you will find the con
-
nections for the sensors (low voltage area) while on the left
hand side you will find the connections for mains and
switching output A1.
General connection rules
If flexible wires are used and the controller is fitted to the
wall, wires must be tied externally in such way that strain
to the controller is avoided.
In this case you must tin or crimp the wire ends.
If required PG9 screws can be fixed at the feed-throughs
if the control is mounted to the wall.
230 V mains connection
Mains power is connected from outside the connector
via an ON/OFF switch.
If the unit is connected with a plug to a socket, the switch
can be omitted.
The unit is designed to work with 230V AC/50Hz. Please
check that your pump has compatible specifications.
All earth wires are connected to the PE-connectors.
The neutral terminals (N) are connected electrically.
Switch output A1 is a 230 V normally open contact which
is activated via speed-control.
Connecting the temperature sensors
The wires for the temperature sensors can be extended:
Up to 15 m length = 2 x 0.5 mm² cable can be used; up to
50m=2x0.75 mm² cable is necessary.
For long connections it is recommended to use shielded
cable.
Do not connect the shielding at the sensor end, just trim
and isolate!
Temperature sensors are without polarity and can be
connected any way.
Sensor wires must be installed away from mains carrying
cables.
Lightning protector module
The SUNGO S is fitted with spike protection on all sensor
terminals. Generally, further protection of the cylinder sen
-
sors is not required.
Sensor T1 (collector) requires installation of sensor con-
nection box SP2 with excess voltage protection.
Safety fuse
Mains voltage area Safety low voltage area
Mains connector
Switch output A1 connector
Mains microfuse 2A/T
Electronic triac switch
Triac control IC
Transformer
for circuit voltage 12 V
Ribbon cable plug
for display circuit
Sensors T1-T3 connectors
Earth potential connector
Figure 2 SUNGO S circuit board components.