WAGO-I/O-SYSTEM 750 Use in Hazardous Environments 71
750-471 4AI U/I Diff Galv
Manual
Version 1.0.0
Table 39: Description of Marking Example According to ATEX and IECEx
Marking
Description
TUEV 07 ATEX 554086 X
IECEx TUN 09.0001 X
Approving authority resp. certificate numbers
Dust
II
Equipment group: All except mining
3 D
Category 3 (Zone 22)
Ex
Explosion protection mark
tc
Type of protection: Protection by enclosure
IIIC
Explosion group of dust
T135°C
Max. surface temperature of the enclosure
(without a dust layer)
Dc
Equipment protection level (EPL)
Mining
I
Equipment group: Mining
M2
Category: High level of protection
Ex
Explosion protection mark
d
Type of protection: Flameproof enclosure
I
Explosion group for electrical equipment for
mines susceptible to firedamp
Mb
Equipment protection level (EPL)
Gases
II
Equipment group: All except mining
3 G
Category 3 (Zone 2)
Ex
Explosion protection mark
nA
Type of protection: Non-sparking equipment
IIC
Explosion group of gas and vapours
T4
Temperature class: Max. surface temperature
135 °C
Gc
Equipment protection level (EPL)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the WAGO 750 and is the answer not in the manual?

WAGO 750 Specifications

General IconGeneral
Power Supply24 VDC
CategoryI/O Systems
Series750
Protection ClassIP20
MountingDIN rail mounting
Communication ProtocolPROFIBUS, CANopen, Modbus

Related product manuals