WAGO-I/O-SYSTEM 750 Diagnostics 67
750-657 IO-Link Master
Manual
Version 1.0.2, valid from FW/HW-Version 02/01
Pos: 83 /Alle Serien ( Allgemeine Module)/Über schriften für alle Seri en/Diagnose - Servic e/Diagnose - Überschr ift 1 @ 4\mod_1240831069 471_21.doc @ 31372 @ 1 @ 1
10 Diagnostics
Pos: 84 /Serie 750 (W AGO-I/O-SYSTEM)/Diagnose/ Feldbuskoppler/- controller/Diagnos e 750-0657 @ 9\mod_1296727 922797_21.doc @ 69150 @ 223 @ 1
The IO-Link master provides two options for diagnosis and event handling – via
the status byte and the Mailbox.
Diagnosis via PROFIBUS coupler is found in the appendix in section "Fieldbus-
Specific Additions" > "PROFIBUS" > "Diagnosis When Using a PROFIBUS
Coupler".
10.1 Diagnosis via the Status Byte
If register communication is disabled (bit 7 in the control byte = 0), status
information of the I/O module and IO-Link ports is displayed via the status byte.
Table 30: Status byte
Status byte
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 GEN_
ERR
PORT4_
ERR
PORT3_
ERR
PORT2_
ERR
PORT1_
ERR
IOLM_
ERR
INT_
ERR
1 Res. Register number of the request (mirrored)
0 Mailbox active (Bit 7)
1 Register communication active
0 No error GEN_ERR
1 Error is pending. Set when one of the bits 0…5 = 1.
0 The device attached to port 4 is not in the fault condition. PORT4_ERR
1 The device attached to port 4 is in the fault condition.
0 The device attached to port 3 is not in the fault condition. PORT3_ERR
1 The device attached to port 3 is in the fault condition.
0 The device attached to port 2 is not in the fault condition. PORT2_ERR
1 The device attached to port 2 is in the fault condition.
0 The device attached to port 1 is not in the fault condition. PORT1_ERR
1 The device attached to port 1 is in the fault condition.
0 The IO-Link master is not in the fault condition. IOLM_ERR
1 The IO-Link master is in the fault condition.
0 No internal errors INT_ERR
1 Internal error. Possible causes:
• 24V field supply missing
• Communication via mailbox and process data faulty.