Loading...
EZ-ZONE PM Limit Express 26 • Specifications
Specifications
Line Voltage/Power
All voltage levels represent minimums and maximums
85 to 264V~(ac), 47 to 63Hz
20 to 28VÅ(ac), +10/-15 percent; 50/60Hz, ±5 percent
12 to 40VÎ(dc)
10VA maximum power consumption (PM3 and PM6)
14VA maximum power consumption (PM4, 8 and 9)
Data retention upon power failure via nonvolatile memory
Compliant with SEMI F47-0200, Figure R1-1 voltage sag requirements @ 24VÅ(ac) or higher
Environment
-18 to 65°C (0 to 149°F) operating temperature
-40 to 85°C (-40 to 185°F) storage temperature
0 to 90 percent RH, non-condensing
Accuracy
Calibration accuracy and sensor conformity: ±0.1 percent of span, ±1°C @ the calibrated ambient temperature
and rated line voltage
Type S, 0.2 percent
Type T, below -50°C; 0.2 percent
Calibration ambient temperature @ 25°C ±3°C (77°F ±5°F)
Accuracy span: 540°C (1000°F) minimum
Temperature stability: ±0.1°C/°C (±0.1°F/°F) rise in ambient maximum
Agency Approvals
cULus
®
UL/EN/CSA C22.2 No. 61010-1 Listed File E185611
cULus
®
ANSI/ISA 12.12.01-2007, CSA-C22.2 No.213-1987, Class 1 Division 2 Groups A, B, C and D, Tempera-
ture Code T4A, File E184390 (optional)
UL
®
50, 4X indoor locations, NEMA 4X, IP65 front seal
CSA C22.2 No. 24 File 158031 (1/32 and 1/16 DIN sizes)
CE, RoHS by design, W.E.E.E.
FM Class 3545 File 3029084
SEMI F47-0200
Serial Communications
Isolated communications
Standard Bus Configuration Protocol
Wiring Termination—Touch-Safe Terminals
Input, power and controller output terminals are touch safe removable 12 to 22 AWG
Use 75°C, Cu conductor only
Universal Input
Thermocouple, grounded or ungrounded sensors
>20MΩinput impedance
Maximum of 2KΩ source resistance (applies to T/C only)
RTD 2- or 3-wire, platinum, 100Ω @ 0°C calibration to DIN curve (0.00385 Ω/Ω/°C)
Process, 4-20mA @ 100Ω, or 0-10VÎ(dc) @ 20kΩ input impedance; scalable