Watlow EZ-ZONE
®
 PM PID Controller  •  12 •  Chapter 2 Install and Wire 
Terminal Definitions for Slots A 
Slot A
Output Terminal Function Configuration
1 2
X1
W1
Y1
common (Any switched dc output can use this common.)
dc- (open collector)
dc+
Switched dc/open collector
output 1: PM _ _ _ C _-_ AAAA _ _
W2
Y2
dc-
dc+
Switched dc
output 2: PM _ _ _ _ C-_ AAAA _ _
F1
G1
H1
voltage or current -
voltage +
current +
Universal Process
output 1: PM _ _ _ F _-_ AAAA _ _
L1
K1
J1
normally open
common
normally closed
Mechanical Relay 5 A, Form C
output 1: PM _ _ _ E _-_ AAAA _ _
L2
K2
normally open
common
NO-ARC 15 A, Form A 
output 2: PM[4, 6, 8, 9] _ _ _ H-_ AAAA _ _
L2
K2
normally open
common
Mechanical Relay 5 A, Form A
output 2: PM _ _ _ _ J-_ AAAA _ _
L1
K1
L2
K2
normally open
common
Solid-state Relay 0.5 A, Form A
output 1: PM _ _ _ K _-_ AAAA _ _
output 2: PM _ _ _ _ K-_ AAAA _ _
Inputs
1
T1
S1
R1
S2 (RTD) or current + 
S3 (RTD), thermocouple -, current -, volts - or potentiom-
eter wiper, thermistor
S1 (RTD), thermocouple + or volts +, thermistor
Universal / Thermistor Input
input 1: all configurations
Slot A
Terminal Definitions for Slot C
Slot C Terminal Function Configuration
98
99
power input: ac or dc+
power input: ac or dc-
all
CC
CA
CB
Standard Bus or Modbus RTU EIA-485 common
Standard Bus or Modbus RTU EIA-485 T-/R-
Standard Bus or Modbus RTU EIA-485 T+/R+
Standard Bus or Modbus
PM _ _ _ _ _-1 AAAA _ _
CF
CD
CE
Standard Bus EIA-485 common
Standard Bus EIA-485 T-/R-
Standard Bus EIA-485 T+/R+
PM _ _ _ _ _-A AAAA _ _
B5
D6
D5
digital input-output common
digital input or output 6
digital input or output 5
PM _ _ 2 _ _-_ AAAA _ _
PM _ _ 4 _ _-_ AAAA _ _
C
Dig I/O 5 & 6
485 Comms
Power
A
Output 2
Output 1
Input 1
B
Back View
Slot Orientation
1/16 DIN PM6
C
A
Power
485 Comms
Dig I/O 5 & 6
Output 1Output 2
Input 1
Back View
Slot Orientation
1/32 DIN PM3