Watlow EZ-ZONE
®
 PM PID Controller  •  83 •  Chapter 9 Features
View or change alarm set points with Low Set 
Point [`A;Lo] and High Set Point [`A;hi] (Operations 
Page, Alarm Menu).
Alarm Hysteresis
An alarm state is triggered when the process value 
reaches the alarm high or alarm low set point. Alarm 
hysteresis defines how far the process must return 
into the normal operating range before the alarm can 
be cleared.
Alarm hysteresis is a zone inside each alarm set 
point. This zone is defined by adding the hysteresis 
value to the alarm low set point or subtracting the 
hysteresis value from the alarm high set point.
View or change alarm hysteresis with Hysteresis 
[`A;hy] (Setup Page, Alarm Menu).
Normal Operating Range
Low Side Alarm Range
High Side Alarm Range
Alarm High Set Point
Alarm Low Set Point
Time
Temperature
Alarm Set Points and Hysteresis
Alarm Hysteresis
Alarm Hysteresis
Alarm Latching
A latched alarm will remain active after the alarm 
condition has passed. It can only be deactivated by 
the user.
An active message, such as an alarm message, 
will cause the display to toggle between the normal 
settings and the active message in the upper display 
and [Attn] in the lower display.
Push the Advance Key to display [ignr] in the 
upper display and the message source in the lower 
display.
Use the Up ¿ and Down ¯ keys to scroll through 
possible responses, such as Clear [`CLr] or Silence 
[`SiL]. Then push the Advance ‰ or Infinity ˆ key 
to execute the action.
See the Keys and Displays chapter and the Home 
Page chapter for more details.
An alarm that is not latched (self-clearing) will 
deactivate automatically when the alarm condition 
has passed.
Turn alarm latching on or off with Latching 
[`A;LA] (Setup Page, Alarm Menu).
Normal Operating Range
Alarm High
Set Point
Time
Temperature
Alarm Low
Set Point
Alarm Response with Hysteresis
The alarm state continues until the 
temperature drops to the Alarm High 
Set Point minus the hysteresis. A 
latching alarm could be turned off by 
the operator at this point. A non-
latching alarm would turn off 
automatically. 
The alarm state begins when the temperature 
reaches the Alarm High Set Point
Process 
Temperature
Alarm Hysteresis
Alarm Silencing
If alarm silencing is on the operator can disable the 
alarm output while the controller is in an alarm 
state. The process value or temperature has to enter 
the normal operating range beyond the hysteresis 
zone to activate the alarm output function again.
An active message, such as an alarm message, 
will cause the display to toggle between the normal 
settings and the active message in the upper display 
and [Attn] in the lower display.
Push the Advance Key to display [ignr] in the 
upper display and the message source in the lower 
display.
Use the Up ¿ and Down ¯ keys to scroll through 
possible responses, such as Clear [`CLr] or Silence 
[`SiL]. Then push the Advance ‰ or Infinity ˆ key 
to execute the action.
See the Keys and Displays chapter and the Home 
Page chapter for more details.
Turn alarm silencing on or off with Silencing 
[`A;Si] (Setup Page, Alarm Menu).
Alarm Blocking
Alarm blocking allows a system to warm up after 
it has been started up. With alarm blocking on, an 
alarm is not triggered when the process tempera-
ture is initially lower than the alarm low set point 
or higher than the alarm high set point. The process 
temperature has to enter the normal operating range 
beyond the hysteresis zone to activate the alarm 
function.
If the EZ-ZONE PM has an output that is func-
tioning as a deviation alarm, the alarm is blocked 
when the set point is changed, until the process value 
re-enters the normal operating range.
Turn alarm blocking on or off with Blocking 
[`A;bL] (Setup Page, Alarm Menu).
Programming the EZ Key/s
You can program the EZ Key either in the Setup 
Menu or with configuration software, such as EZ-