Watlow EZ-ZONE
®
PM PID Controller 39 Chapter 5 Operations Page
Operations Page
Display
Parameter name
Description
Range Default
Parameter
Appears in
Menu When
Modbus Rela-
tive Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[`S;ti]
[ S.ti]
Profile Status
*Step Time Remain-
ing
View or change the
time remaining for
the current step.
Step is displayed in
seconds. If the time
exceeds 9,999 sec-
onds, the display
will show 9,999 and
remain there while
the control contin-
ues to decrement
internally. Once the
remaining time is
equal to or less than
9,999 the display will
represent the actual
seconds remaining.
As an example, if a
three-hour soak time
is currently being
monitored, the first
value displayed will
be 9,999, and the
display will remain
at 9,999 until the
remaining time is ap-
proximately equal to
2 hours and 46 min-
utes. At this point
the display will track
the actual seconds
remaining.
0 to 9,999.000 seconds 0 Always Instance 1
Map 1 Map 2
2536 4356
0x7A (122)
1
9
- - - - float
RW
[Ent1]
[Ent1]
Profile Status
Active Event Out-
put 1
View or change the
event output states.
[`off] Off (62)
[``on] On (63)
Off Always Instance 1
Map 1 Map 2
2546 4512
0x7A (122)
1
0xE (14)
- - - - uint
RW
[Ent2]
[Ent2]
Profile Status
Active Event Out-
put 2
View or change the
event output states.
[`off] Off (62)
[``on] On (63)
Off Always Instance 1
Map 1 Map 2
2548 4514
0x7A (122)
1
0xF (15)
- - - - uint
RW
[``JC]
[ JC]
Profile Status
Jump Count Re-
maining
View the jump counts
remaining for the cur-
rent loop. In a profile
with nested loops,
this may not indi-
cate the actual jump
counts remaining.
0 to 9,999 0 Always Instance 1
Map 1 Map 2
2538 4358
0x7A (122)
1
0xA (10)
- - - - uint
R
Profile Status
Profile State
Read currentProfile
state.
off (62)
Running (149)
Pause (146)
Instance 1
Map 1 Map 2
2522 4342
0x7A (122)
1
2
- - - - uint
R
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with
other inter- faces.
* Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E: EEPROM
S: User
Set