Watlow EZ-ZONE
®
PM PID Controller • 56 • Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter name
Description
Range Default
Parameter
Appears
in Menu
When
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[`r;Lo]
[ r.Lo]
Output (1 process)
Range Low
Set the minimum
value of the retrans-
mit value range in
process units. When
the retransmit source
is at this value, the
retransmit output will
be at its Scale Low
value.
-1,999.000to9,999.000°F
or units
-1,128.000to5,537.000°C
0.0°For
units
-18°C
Always if
digit 6 of
the part
number is
an "F".
Instance 1
Map 1 Map 2
740 860
0x76 (118)
1
0xB (11)
101 float
RWES
[`r;hi]
[ r.hi]
Output (1 process)
Range High
Set the maximum
value of the retrans-
mit value range in
process units. When
the retransmit source
is at this value, the
retransmit output will
be at its Scale High
value.
-1,999.000to9,999.000°F
or units
-1,128.000to5,537.000°C
9,999.0°F
or units
5,537.0°C
Always if
digit 6 of
the part
number is
an "F".
Instance 1
Map 1 Map 2
742 862
0x76 (118)
1
0xC (12)
102 float
RWES
[`o;CA]
[ o.CA]
Output (1 process)
Calibration Offset
Set an offset value for
a process output.
-1,999.000to9,999.000°F
or units
-1,110.555to5,555.000°C
0.0°For
units
0.0°C
Always if
digit 6 of
the part
number is
an "F".
Instance 1
Map 1 Map 2
732 852
0x76 (118)
1
7
105 float
RWES
[Alm]
[`Set]
Alarm Menu
[`A;ty]
[ A.ty]
Alarm (1 to 4)
Type
Select whether the
alarm trigger is a
fixed value or will
track the set point.
[`oFF] Off (62)
[PR;AL] Process Alarm (76)
[dE;AL] Deviation Alarm
(24)
Off Always Instance 1
Map 1 Map 2
1508 1908
Offset to next
instance (Map
1 & Map 2)
equals +60
0x6D (109)
1 to 4
0xF (15)
20 uint
RWES
[`Sr;A]
[ Sr.A]
Alarm (1 to 4)
Source Function A
Select what will trig-
ger this alarm.
[``Ai] Analog Input (142)
[PWr] Power, Control
Loop (73)
[``Pu] Process Value
(241)
[`Lnr] Linearization (238)
[CUrr] Current (22)
Type is not
set to Off
or devia-
tion..
Instance 1
Map 1 Map 2
1512 1912
Offset to next
instance (Map
1 & Map 2)
equals +60
0x6D (109)
1 to 4
0x11 (17)
21 uint
RWES
[`is;A]
[ iS.A]
Alarm (1 to 2)
Source Instance A
Set the instance of
the function selected
above.
1 or 2 1 Type is not
set to Off.
Instance 1
Map 1 Map 2
1514 1914
Instance 2
Map 1 Map 2
1564 1974
0x6D (109)
1 to 2
0x12 (18)
22 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with
other interfaces.
* Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E:
EE-
PROM
S:
User
Set