SECTION 9 AERTRIM OPERATION
OMM-0137_E • GF-211 12/13/2019 Technical Support (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 136 of 153
9.6 AERtrim MAINTENANCE and TROUBLESHOOTING
The AERtrim system, which maximizes blower efficiency, depends on the O
2
sensor. The AERtrim
system needs only minimal maintenance. It is recommended that you inspect the oxygen
sensor for accuracy every 12 months by comparing it to a sensor reading from a properly
calibrated flue analyzer. This is strongly advised because contaminated air or gas supplies may
cause impurity buildup and shift the calibration point. An offset value of ±3.0% can be entered in
the O2 Offset parameter in the AERtrim Settings screen (Main Menu Advanced Setup
Performance AERtrim AERtrim Settings) to correct the reading during manual calibration.
If the sensor has a large amount of offset, a replacement may be required soon.
Occasional software updates to the device may be required.
TABLE 9-1: AERtrim General Warnings
Warning
Cause
Possible Solutions
O2 Percentage Low
O
2
Levels less than 2% for more
than 30 seconds (auto-reset when
valve comes back in range}
Dirty filter or poor combustion
calibration recalibrate unit
O
2
Offset too low Increase
Offset value
Bad Sensor-Replace
O2 Sensor Malfunction
O
2
Levels less than -4% or more
than 24% for more than 10 seconds
{manual clearing of this fault is
required}
Bad Sensor-Replace
Communication Issue check
wires and connections
Warning 02 Level High
O
2
Levels > 9% and < 24% for more
than 30 seconds {auto-reset when
value comes back in range}
Gas Pressure Regulator or Air
Blower Problem, or bad
Combustion Calibration
O
2
Offset too high
Bad Sensor-Replace
O2 Sensor Out of
Range
Sensor auto calibration offset
required is more than ±3%
Reset Unit-Recalibrate Sensor
Bad Sensor-Replace
Bad ECU-Replace (Rare)
O2 Warning Service
Required
If the O
2
level is outside of its limits
for more than 5 minutes.
For example:
1) Reading < Lower Limit
& Blower Voltage = BV Limit
OR
2) Reading > Upper Limit
& Blower Voltage = BV Limit
Gas Supply, Air Filter, or Air
Blower issue
Bad Sensor-Replace