NOTE:
Both Header Temp Sensor and 4-20ma Direct Drive must be wired. See the Edge Controller
Manual (OMM-0139, GF-213) for more information.
Step 1: HEADER TEMP SENSOR WIRING – BST MANAGER Unit
1. On the BST Manager unit, connect the Header Temp Sensor (P/N 24410) to the I/O
board terminal strip J3, terminals 4 (Supply Header +) and 5 (Supply Header -).
2. Connect the shield to any Shield terminal, such as terminal 3 or 8 on strip J3.
NOTES:
• The Header Temp Sensor must be installed between 2 and 10 feet (0.61 and 3.1m)
downstream of the LAST boiler in the plant’s supply water header.
• Shielded pair 18 - 22 AWG cable is recommended for Header Temp Sensor wiring.
There is no polarity to be observed. The ground for the shield is at the Shield terminal
on the I/O the board. The sensor end of the shield must be left free and ungrounded.
Step 2: DIRECT WIRED 0-20mA or 4-20mA WIRING – BST MANAGER Unit
1. Connect the 4-20mA or 0-20mA terminals from the Direct Drive source to the I/O board
strip J3, terminals 6 (Remote Analog In +) and 7 (Remote Analog In –) on the BST
Manager.
2. Connect the shield to any Shield terminal on the I/O board, such as terminal 3 or 8.
NOTES:
• Shielded pair 18 - 22 AWG cable is recommended for this connection. Polarity must be
observed.
• The ground for the shield is at the driver signal source.
Continued on next page