Benchmark Platinum-Edge [II]: Operation-Service Manual
SECTION 4 – INITIAL START-UP
OMM-0137_E • GF-211 • 12/13/2019 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 50 of 153
PROPANE Combustion Calibration Instructions
TABLE 4-6b: PROPANE Final Valve Positions: BMK5000 & 6000
NOTE:
If NOx readings exceed the target values in Table 4-6a and 4-6b, increase the O
2
level up to
1% higher than the listed calibration range shown in the table. Record the increased O
2
value
on the Combustion Calibration sheet.
26. If the oxygen level at the lowest valve position is too high, and the Blower voltage is at the
minimum value, you can adjust the TAC screw, which is recessed in the top of the Air/Fuel
Valve (see Figure 4-3). Rotate the screw 1/2 turn clockwise (CW) to add fuel and reduce
the O
2
to the specified level. Recalibration MUST be performed again from 60% or 50%
down to the lowest valve position after making a change to the TAC screw.
This completes the PROPANE gas combustion calibration procedure.
4.5 REASSEMBLY
Once the combustion calibration adjustments are properly set, the unit can be reassembled for
service operation.
1. Set the Enable/Disable switch in the Disable position.
2. Disconnect AC power from the unit.
3. Shut off the gas supply to the unit.
4. Remove the manometer and barbed fittings and reinstall the NPT plug using a suitable
pipe thread compound.
5. Remove the combustion analyzer probe from the 1/4” vent hole in the exhaust manifold
and then replace the 1/4” NPT plug in the vent hole.